Roman Piszcz

Live support:

Monday - Friday 6AM - 6PM PST

3210978 Phoenix Contact Terminal Blocks

Phoenix Contact 3210978 Protective conductor double-level terminal block, connection method: Push-in connection, cross section: 0.14 mm² - 4 mm², AWG: 26 - 12, width: 5.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15
Phoenix Contact

Part#:3210978

Manufacturer:Phoenix Contact

Product Lifecycle:Active

In-stock parts: 5453

Apr 21, 2025

Protective conductor double-level terminal block, connection method: Push-in connection, cross section: 0.14 mm² - 4 mm², AWG: 26 - 12, width: 5.2 mm, color: gray, mounting type: NS 35/7,5, NS 35/15

About the manufacturer: Phoenix Contact is one of the manufacturers that offers Terminal Blocks that you can order at marketplace.quotebeam.com. Phoenix Contact manufactures industrial electrical and electronic technology products that offer power, protection, connectivity, and automation for systems and equipment.

Check out the 3210978 Phoenix Contact price in the box on the right side or send a quick quote.

Product Details

  • Insulating material
    PA
  • Nominal cross section
    2.5 mm²
  • Degree of pollution
    3
  • Connection in acc. with standard
    CSA
  • Open side panel
    Yes
  • Surge voltage test setpoint
    7.3 kV
  • Result of flexion and pull-out test
    Test passed
  • Tensile test result
    Test passed
  • Tight fit on carrier
    NS 35
  • Result of temperature-rise test
    Test passed
  • Proof of thermal characteristics (needle flame) effective duration
    30 s
  • Test specification, oscillation, broadband noise
    DIN EN 50155 (VDE 0115-200):2008-03
  • Test directions
    X-, Y- and Z-axis (pos. and neg.)
  • Color
    gray
  • Result of tight fit on support
    Test passed
  • Requirements, voltage drop
    ≤ 3.2 mV
  • Conductor cross section short circuit testing
    4 mm²
  • Result of thermal test
    Test passed
  • Number of levels
    2
  • Rated surge voltage
    6 kV
  • Overvoltage category
    III
  • Nominal current IN
    24 A
  • Back of the hand protection
    guaranteed
  • Result of surge voltage test
    Test passed
  • Bending test conductor cross section/weight
    0.14 mm² / 0.2 kg
  • Setpoint
    1 N
  • Short-time current
    0.48 kA
  • Oscillation, broadband noise test result
    Test passed
  • Acceleration
    30g
  • Shock form
    Half-sine
  • Static insulating material application in cold
    -60 °C
  • Calorimetric heat release NFPA 130 (ASTM E 1354)
    28 MJ/kg
  • End cover width
    2.2 mm
  • Conductor cross section solid min.
    0.14 mm²
  • Conductor cross section AWG max.
    12
  • Number of connections
    4
  • Flammability rating according to UL 94
    V0
  • Maximum power dissipation for nominal condition
    0.77 W (the value is multiplied when connecting multiple levels)
  • Nominal voltage UN
    500 V
  • Finger protection
    guaranteed
  • Result of power-frequency withstand voltage test
    Test passed
  • Bending test rotation speed
    10 rpm
  • Bending test turns
    135
  • Conductor cross section tensile test
    4 mm²
  • Result of aging test
    Test passed
  • Test spectrum
    Service life test category 2, bogie-mounted
  • ASD level
    6.12 (m/s2)2/Hz
  • Shock duration
    18 ms
  • Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21))
    130 °C
  • Fire protection for rail vehicles (DIN EN 45545-2) R22
    HL 1 - HL 3
  • Length
    68 mm
  • Connection method
    Push-in connection
  • Conductor cross section flexible, with ferrule without plastic sleeve max.
    2.5 mm²
  • Operating temperature
    -60 °C ... 105 °C (max. short-term operating temperature 130°C)
  • Ambient temperature (actuation)
    -5 °C ... 70 °C
  • ECLASS 5.0
    27141100
  • ECLASS 5.1
    27141100
  • ETIM 4.0
    EC000901
  • UNSPSC 11
    39121410
  • Insulating material group
    I
  • Maximum load current
    30 A (with 4 mm² conductor cross section, rigid)
  • Shock protection test specification
    DIN EN 50274 (VDE 0660-514):2002-11
  • Power frequency withstand voltage setpoint
    1.89 kV
  • Checking the mechanical stability of terminal points (5 x conductor connection)
    Test passed
  • Tractive force setpoint
    60 N
  • Result of voltage-drop test
    Test passed
  • Short circuit stability result
    Test passed
  • Ageing test for screwless modular terminal block temperature cycles
    192
  • Test duration per axis
    5 h
  • Test specification, shock test
    DIN EN 50155 (VDE 0115-200):2008-03
  • Number of shocks per direction
    3
  • Specific optical density of smoke NFPA 130 (ASTM E 662)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R24
    HL 1 - HL 3
  • Pitch
    5.2 mm
  • Height NS 35/15
    55 mm
  • Conductor cross section flexible min.
    0.14 mm²
  • Conductor cross section flexible, with ferrule without plastic sleeve min.
    0.14 mm²
  • Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum
    0.5 mm²
  • Ambient temperature (storage/transport)
    -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
  • ECLASS 4.1
    27141100
  • ECLASS 11.0
    27141141
  • ECLASS 9.0
    27141141
  • ETIM 2.0
    EC000901
  • UNSPSC 13.2
    39121410
  • UNSPSC 19.0
    39121410
  • Test frequency
    f1 = 5 Hz to f2 = 250 Hz
  • Shock test result
    Test passed
  • Surface flammability NFPA 130 (ASTM E 162)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R23
    HL 1 - HL 3
  • Width
    5.2 mm
  • Note
    Please observe the current carrying capacity of the DIN rails.
  • Conductor cross section flexible max.
    4 mm²
  • Conductor cross section flexible, with ferrule with plastic sleeve min.
    0.14 mm²
  • Internal cylindrical gage
    A3
  • ECLASS 10.0.1
    27141141
  • ECLASS 4.0
    27141100
  • ECLASS 7.0
    27141141
  • ETIM 6.0
    EC000901
  • UNSPSC 7.0901
    39121410
  • UNSPSC 20.0
    39121410
  • Relative insulation material temperature index (Elec.; UL 746 B)
    130 °C
  • Smoke gas toxicity NFPA 130 (SMP 800C)
    passed
  • Fire protection for rail vehicles (DIN EN 45545-2) R26
    HL 1 - HL 3
  • Height NS 35/7,5
    47.5 mm
  • Conductor cross section solid max.
    4 mm²
  • Conductor cross section AWG min.
    26
  • Permissible humidity (storage/transport)
    30 % ... 70 %
  • China RoHS
    Environmentally friendly use period: unlimited = EFUP-e
  • ECLASS 6.0
    27141100
  • ETIM 7.0
    EC000901
  • UNSPSC 18.0
    39121410
  • Conductor cross section flexible, with ferrule with plastic sleeve max.
    2.5 mm²
  • Stripping length
    8 mm ... 10 mm
  • Ambient temperature (assembly)
    -5 °C ... 70 °C
  • ETIM 3.0
    EC000901
  • UNSPSC 6.01
    30211811
  • UNSPSC 12.01
    39121410
  • UNSPSC 21.0
    39121410

Product condition

ORIGINAL PACKAGING

SURPLUS ORIGINAL PACKAGING - 100% unused and in original packaging


This item can ship within 24h!

1-year warranty

$9.96

Stock:

5,453

Select Qty:

$9.96

$9.96 each

By purchasing this item, you agree to the Terms & Conditions

Quotebeam is NOT an authorized distributor of Phoenix Contact

Shipping and Delivery Worldwide

calculate costs and time


Secure Payment Processing

with money back guarantee


1 year warranty

on all parts


Responsive Customer Support

we're here to help!

Need more details?

Feel free to chat with us or check our FAQ

Phoenix Contact Disclaimer:

The product is unused surplus. Quotebeam is not an authorized surplus dealer or affiliate for the Manufacturer of this product. Products may feature older date codes or be from an earlier series than what is currently available from the manufacturer or authorized dealers. Because Quotebeam is not an authorized distributor of this product, the Original Manufacturer’s warranty does not apply. While many Phoenix Contact Controls products will have firmware already installed, Quotebeam makes no representation as to whether a Controls product will or will not have firmware and, if it does have firmware, whether the firmware is the revision level that you need for your application. Quotebeam also makes no representations as to your ability or right to download or otherwise obtain firmware for the product from Phoenix Contact, its distributors, or any other source. Quotebeam also makes no representations as to your right to install any such firmware on the product. Quotebeam will not obtain or supply firmware on your behalf. It is your obligation to comply with the terms of any End-User License Agreement or similar document related to obtaining or installing firmware.

Relevant products

Do you have questions?

We’re here for you ✨

We are a proud member of:

Association for High Technology Distribution LogoAssociation for Advancing Automation LogoThe International Society of Automation Logo